Automatic Side-stream Filtration System + Intelligent Backwash: AFS Series Self-Cleaner Significantly Reduces Cleaning Frequency of Cooling Tower Basin
Common lssues During Cooling Tower Operation
During long-term cooling tower operation, suspended solids in circulating water — such as dust, silt, and microbial slime — gradually settle in the bottom basin. Due to low flow velocity and insufficient hydraulic disturbance, these impurities easily accumulate, forming sediment that thickens and hardens over time. If not removed promptly, this buildup directly reduces heat dissipation efficiency and increases energy consumption. Therefore, regular basin cleaning is a key maintenance measure to ensure stable operation of your cooling tower system.

During actual cooling tower cleaning, the following extreme situations are frequently observed:
-
Sludge buildup several centimeters deep — sometimes completely covering the drain outlet, severely compromising drainage.
-
Hardened scale formation — after prolonged drying, sediments harden into solid scale that cannot be removed by conventional flushing; mechanical scraping is required.
-
Frequent drain piping blockages — sludge and grime accumulate at pipe elbows and valves, rendering the drainage system ineffective and preventing proper wastewater discharge.

The main reasons are: there aren't enough staff on site, the cooling tower can't be shut down for long, and cleaning inside the tower is difficult. As a result, most cooling tower basins are cleaned much less often than they should be—some have never been cleaned at all. This directly worsens water quality and increases energy consumption for the cooling system.
These problems are quietly increasing cooling tower equipment wear and electricity costs. Sediment buildup causes gradual wear that continuously affects the cooling tower's operating efficiency.
►The AFS Series Self-Cleaner: A Proactive Filtration Solution for Cooling Towers
The water-saving, labor-saving, and highly efficient cooling tower purification solution provided by NEWIN regarding above problems is the AFS series self-cleaner — a Cooling Tower Automatic Filtration System that uses Active Side-Stream Filtration + Intelligent Backwash to continuously purify water without interfering with the main loop, reducing blowdown, chemical dosing, and downtime, while cutting O&M costs and maintaining cooling efficiency.


Key Advantages Over Traditional Solutions
|
Traditional Approach |
Intelligent Changes Brought by the AFS Series |
Success Stories |
|
|
![]() |
Actual Results: Significantly Reduced Cleaning Frequency of the Bottom Basin
Based on NEWIN's operating data collected from various working conditions:
|
Site conditions |
Base pan cleaning frequency without AFS |
Base pan cleaning frequency with AFS |
|
General indoor environment |
Every 3 to 6 months |
A check every 1 to 2 years is sufficient, and most require no cleaning |
|
Dusty environment |
Every 1 to 2 months |
A quick rinse every 6 to 12 months is all that is required |
AFS filtration system parameters specify basin cleaning area (see data sheet). Match nozzle coverage with basin dimensions for consistent anti-sedimentation performance.
|
Model |
AFS-25 |
AFS-40 |
AFS-50 |
AFS-65 |
AFS-80 |
AFS-100 |
AFS-125 |
AFS-150 |
AFS-200 |
AFS-250 |
AFS-300 |
|
|
Filtration Flow Rate |
4-6 |
11-16 |
18-25 |
30-42 |
45-63 |
71-99 |
110-155 |
157-223 |
283-396 |
442-618 |
636-890 |
|
|
Pump |
0.75 |
1.5 |
2.2 |
3 |
5.5 |
7.5 |
11 |
15 |
22 |
30 |
55 |
|
|
Dimension |
L |
1500 |
1650 |
1750 |
2100 |
2200 |
2850 |
3340 |
3550 |
4300 |
5200 |
6000 |
|
W |
600 |
600 |
700 |
700 |
800 |
1100 |
1280 |
1420 |
1600 |
1880 |
2250 |
|
|
H |
1200 |
1500 |
1600 |
1800 |
2000 |
2400 |
2700 |
3060 |
3900 |
4050 |
4400 |
|
|
Dry weight(kg) |
220 |
240 |
270 |
310 |
450 |
540 |
820 |
980 |
1430 |
1890 |
2550 |
|
|
Operating weight |
230 |
270 |
310 |
380 |
570 |
780 |
1260 |
1730 |
2880 |
4860 |
8550 |
|
|
Recommended Basin Cleaning Area(m2) |
2.4 |
6.4 |
10.0 |
16.8 |
25.2 |
39.6 |
62.0 |
89.2 |
158.4 |
247.2 |
356.0 |
|
For users needing to reduce manual basin cleaning and improve operational stability, the AFS side-stream filter offers proven technical and economic value. Contact us at sales@newinmachine.co for a customized solution to improve cooling tower efficiency, prolong service life, and increase production benefits.